Canal lock sequencers - rung listing (CNTR 300) RIGHT SEQUENCER SQI(Right_Array_I,1487,Local:1:I.Data,Cntr2) SQO(Right_Arr_O,47,Hold_Right_O,Cntr2) LEFT SEQUENCER XIC(TEST) SQI(Left_Arr_I,479,Local:1:I.Data,Controlling) SQO(Left_Arr_O,31,Hold_left_O,Controlling) SEQUENCER TABLES (decimal) Pos Left_Arr_I Left_Arr_O Right_Array_I Right_Arr_O 0 19 0 1027 0 1 23 8 1035 4 2 150 1 1289 2 3 198 17 329 34 4 71 0 75 0 5 75 4 71 8 6 265 2 134 1 7 11 0 7 0 8 27 0 1031 0 INPUT BITS (Local:1:I.Data) 0 GLC gate left closed 6 SLOG ship in the lock 1 GRC gate right closed 7 GLO gate left open 2 WLL water level low 8 GRO gate right open 3 WLH water level high 9 SRG ship at the right gate 4 SFL ship from left 10 SFR ship from right 5 SLG ship at the left gate OUTPUT BITS 0 OGLS open left gate 3 DWL decrease water level 1 OGRS open right gate 4 FLS free sign, left 2 IWL increase water level 5 FRS free sign, right